Downloads
Abstract
For a practical Frequency Response Analysis (FRA) interpretation applicable to power transformers, frequency dependent electrical parameters of the core and windings in broad frequency range should be identified through non-destructive measurements. Since the core parameters are determined in Part I, electrical parameters of windings (resistances, capacitances) and leakage paths surrounding windings (leakage/zero-sequence impedances) of a distribution transformer will be discussed in this paper. Due to the fact that most parameters associated with the windings currently can only be measured at or around power frequency through diagnostic testing methods, the practical parameter-based FRA interpretation is not possible. To deal with this problem, the paper proposes a new approach based on the combination of different measured driving-point impedances and relevant analysis of the duality-based equivalent circuit in determining frequency dependent parameters associated with transformer windings. Results show that the physical FRA interpretation can be reasonable obtained for the test transformer in low and medium frequency range.
Issue: Vol 20 No K3 (2017)
Page No.: 11-17
Published: Jun 30, 2017
Section: Engineering and Technology - Research article
DOI: https://doi.org/10.32508/stdj.v20iK3.1077
Download PDF = 780 times
Total = 780 times
Most read articles by the same author(s)
- Khoi Dinh Anh Pham, Measurement -based electrical parameters of power transformers for Frequency Response Analysis interpretation - Part I: Core analysis , Science and Technology Development Journal: Vol 20 No K3 (2017)