CIGRE, IEC and IEEE have recently approved the technique of Frequency Response Analysis (FRA) as an application tool for diagnosis of mechanical failures in power transformer’s active part, i.e., windings, leads and the core. The diagnosis is based on the discrepancy between frequency responses measured on power transformers mainly at different time points. In Vietnam, utilities such as Power Transmission Companies and Power Corporations are investigating this technique for application on their power transformers.


Mechanical failures in power transformers cause changes on measured frequency responses starting from a medium frequency range, from several hundreds of Hz or tens of kHz depending on transformer/winding type and power. For a reliable diagnosis, the understanding of transformer/winding structure on measured frequency responses is of importance; thus, the international standards suggested the simulation approach with physical distributed transformer circuits should be exploited.


The development of physical distributed circuits of power transformers normally needs availability of internal transformer structure and material properties for an analytical approach. However, for in-service power transformers, this task is challenging since the required data are not available.


For a feasible application of the simulation based FRA interpretation, this paper introduces an investigation on the development of a distributed equivalent circuit of an in-service 6.5 MVA 47/27.2 kV Yd5 power transformer. The result of this investigation is a feasible approach in determining electrical parameters in a physical distributed circuit, which supports analysis of frequency responses measured at transformer terminals for real application on in-service power transformers of utilities.






Author's Affiliation
Article Details

Issue: Vol 20 No K1 (2017)
Page No.: 58-66
Published: Mar 31, 2017
Section: Engineering and Technology - Research article
DOI: https://doi.org/10.32508/stdj.v20iK1.415

 Copyright Info

Creative Commons License

Copyright: The Authors. This is an open access article distributed under the terms of the Creative Commons Attribution License CC-BY 4.0., which permits unrestricted use, distribution, and reproduction in any medium, provided the original author and source are credited.

 How to Cite
Anh Khoi Pham, D. (2017). Application of Frequency Response Analysis for in-service power transformers. Science and Technology Development Journal, 20(K1), 58-66. https://doi.org/https://doi.org/10.32508/stdj.v20iK1.415

 Cited by



Article level Metrics by Paperbuzz/Impactstory
Article level Metrics by Altmetrics

 Article Statistics
HTML = 2138 times
Download PDF   = 894 times
Total   = 894 times